I. Functional characteristic
1.Measure the transformer load current, load loss, short-circuit voltage, short circuit (load)
losses, capability.
2.Three measurement Methods.
3.Do three-phase transformer no-load, load test, the instrument can automatically
determine the wiring is correct, and shows three-phase voltage and current vector map.
4.Single machine can do the following 100KVA distribution transformer full load current
experiment; in one third of the rated current, complete 250KVA distribution transformer
load the following test (in one third of the rated current, the instrument can be converted
to load loss under rated current parameters, the machine is mainly used in the test bed
with integrated supporting the use of transformers.
5.All the related test results are automatically corrected. Instrument can automatically
such as: the waveform correction, temperature correction, non-rated voltage correction,
calibration, and other non-rated current correction, so that more accurate test results.
6.320x240 large screen, high brightness LCD display, full Chinese menu and operations
to achieve prompt and friendly man-machine dialogue, touch buttons make the
operation more convenient, wide LCD with brightness adjustment, can be adapted to
the various summer and winter season.
7.Comes with real-time clock, automatically recording test date, time, the preservation of
favorable results, management.
8.Panel-type thermal printer, the scene quickly print test results.
9.Data (test sample set, the measurement results, the test of time, etc.) with power-down
storage and browsing features, you can store 500 set of experimental results with
computer on-line data transfer.
10.Allows an external voltage transformer and current transformer for extended range of
measurement, any measurable parameter is the test product.
II. Main technical indicators
1.Test Item
1)Uab,Ubc,Uca;
RMS phase voltage
2)/Uab,/Ubc,/Uca;
Average value of three-phase AC voltage
3) Ia,Ib,Ic;
Three-phase current RMS
4)Percentage of no-load loss and no-load current:Po,Io%;
5)Load loss, impedance voltage, and the percentage of short-circuit impedance:Pt,ekt,Zt;
6)Any given temperature, load loss, the percentage impedance voltage and short circuit impedance;
7)Any given temperature, load loss, the percentage impedance voltage and short circuit impedance.
2.Main technical parameters
1)Capacity measuring range : 30kVA ~ 31500kVA
2)Current measuring range: 0 -100A auto-switch the measurement range
3)Current measurement accuracy: ± (0.2% + 3digits)
4)Voltage measurement range: Line Voltage0-750V;phase voltage 0-450V, auto-switch the measurement range
5)Voltage measurement accuracy: ± (0.2% + 3digits)
6)Insulation resistance: > 100M ohm
7)Leakage current: <3.5mA
8)Dielectric strength: the power connection on the chassis can withstand: 1500V
9)External transformer can broaden the scope of measurement instruments;
10)Frequency Range: 40 ~ 65Hz, accuracy class 0.2;
11)Power Input: AC220V ± 10%;
12)Transport size: 470*370*320mm;
13)Weight: GW/NW: 16kgs/10kgs
III. Panel
IV. Accessaries
Sr no |
Description |
Qty |
1 |
Host |
1 unit |
2 |
Power supply cable |
1 unit |
3 |
Test cables |
1 set |
4 |
Fuse |
3 units |
5 |
Print paper |
2 units |
6 |
Calibration |
1 unit |
8 |
Operating manual |
1 unit |