I. Overview
The National Electric Power Department's Preventive Test Procedures requires periodic turns ratio or voltage ratio tests, including semi-finished and finished products in the production process, transformers before operation and during operation in the power system. The traditional variable ratio bridge operation is cumbersome, the reading is not intuitive, and the necessary conversion is required, and the test result only reflects the one-phase transformation ratio. The instrument overcomes the shortcomings of the traditional variable ratio bridge test, and completes the three-phase ratio test at one time, and the test speed is fast and the accuracy is high, which greatly improves the test efficiency.
II. Security measures
1. Please read this operation manual carefully before using this instrument.
2. This instrument can be used indoors and outdoors, but should avoid rain, corrosive gas and excessive dust.
3. The instrument should avoid severe vibration.
4. The maintenance, care and adjustment of the instrument should be carried out by professionals.
5. The yellow, green and red of the test clamps are not connected to a, b and c of the transformer respectively.
6. Do not connect the high and low voltage cables.
7. Use only the yellow and green clips when measuring single-phase transformers. The red test clip should be left floating.
III. Performance characteristics
1.Test range is wide, up to 10,000.
2.Test speed is fast, complete the single phase test in 10 seconds.
3. Z-shaped connection transformer test.
4. Blind measurement ratio, group test, tap position test function.
5. No power down clock and date display, data storage function (can store 50 sets of test data).
6. High and low voltage reverse connection protection.
7, Transformer short circuit, turn-to-turn short circuit protection.
8. Thermal printer output function, fast, silent.
9. Small size and light weight.
10. AC/DC power supply mode, It can be used with or without electricity on site.
IV. Technical indicator
1. Range: 0.9~10000
2. Accuracy: 0.1%±2 words (below 500);
0.2%±2 words (500~2000);
0.3%±2 words (2000~4000);
0.5% ± 2 words (4000 or more).
3. Resolution: minimum 0.0001.
4. Output voltage: 160v/10v (automatic selection).
5. Working power:
AC: External AC power supply is required,AC220v ± 10%, 50Hz.
DC: No need for external power supply, Lithium battery in instrument.
6. Working temperature: -10ºC~40ºC.
7. Relative humidity: ≤ 80%, no condensation
V. Panel introduction
- Power switch.
- Power supply
- LV port
- HV port
- LCD
- Battery power indicator
- Operation button
- Printer
- Ground
- Charging
- DC indicator
VI.Accessory
Sr no |
Description |
Qty |
1 |
Host of tester |
1 unit |
2 |
Test cables |
1 set |
3 |
Power supply cable |
1 unit |
4 |
Earth cable |
1 unit |
5 |
Print paper |
1 unit |
6 |
Adaptor |
1 unit |
7 |
Portable bag |
1 unit |
8 |
Carrying trap |
1 unit |
9 |
Operating manual |
1 unit |
10 |
Calibration report |
1 unit |