VLF Advantage
1.AC Withstand voltage testing, Voltage & current curve display.
2.Tan delta (tgδ test for option), capacitance (μF) and IR (Ω) Test without external device (for buyer's option).
3.Partial discharge testing without external device .
4.DC withstandi voltage test,DC leakage current measurement (for buyer's option).
5."IEE 400.2" Analysis of Tan delta test result.
6.Safe Optical isolation technology.
7. Easiest to use Fully automatic microcontroller.
8. H/L voltage closed loop negative feedback control circuit, output no capacity rise effect.
9. Built-in printer.
10. Built-in protective resistors.
11. Colour Touch LCD (154*86mm)operation, True sine wave output.
12. Real-time display of actual output waveform.
13. Ergonomic, menu guided, large colour touch screen
14. Storage of test results for later retrieval and print.
15. Over voltage and current protected.
16.Auto variable frequency 0.1Hz, 0.05Hz, 0.02 Hz, 0.01 Hz.
17. 60 mins continuous working;
18. Data of current, voltage and waveform directly sampled at HV side.
19. Rugged and reliable design less prone to failure from transients.
20. Invatation Patent
21. Portable: Control unit + Booster (Tank)
22. CE mark.
23. RS232 for option.
24. Remote control system for option
Specification
1.Power: 220V ± 10% AC (110V can be customized), 50/60Hz, single phase;
2.Output-Voltage (Peak): 1 to rated value (KV), details see the below table;
3.Output frequency: 0.1Hz, 0.05Hz, 0.02 Hz, 0.01 Hz (auto variable frequency);
4.Load: 0.5μF (approx 6,000 ft of cable) @ 0.1 Hz
1.0μF (approx 12,000 ft of cable) @ 0.05 Hz
2.5μF (approx 30,000 ft of cable) @ 0.02 Hz
5.0μF (approx 60,000 ft of cable) @ 0.01 Hz
5. Stability of frequency: Fluctuation < 0.5%;
6. Measurement accuracy: ±3%;
7. Positive and negative voltage peak error: ≤3%;
8. Voltage waveform distortion: ≤5%;
9. Construction: 1 Control unit + 1 Booster (≤60KV set); 1 Control unit + 2 Boosters(≥60KV set).
10. Ambient conditions of use: temperature Indoor and outdoor : -10ºC ~ + 50ºC.
11. Humidity:≤85%
12. Technical indexes of VLF tgδ test (for option):
1) tgδ test voltage range: 1 to 40KV (Only one booster can be used for tan delta test if 2 boosters set)
2) Measurement voltage accuracy: 3%
3) Dielectric loss test frequency: 0.1Hz
4) Measurement range: 0.01×10-3- 655.35×10-3
5) Dielectric loss accuracy: 1x10-4
6) Dielectric loss resolution: 1x10-5
7) Capacitance measurement range: 0.001μF-10μF
8) Celectric capacity resolution: 0.001μF
9) Current measurement range: 0-59mA
10) Current resolution: 0.1mA
11) Insulation resistance: 0.01GΩ-65.53GΩ
12) Insulation resistance resolution: 10MΩ
13.Main technical indexes of VLF PD test :
1) Partial discharge measurement range: 0.1pc-5000pc
2) Partial discharge detection sensitivity: 0.1pc
3) Capacitance range: 0.001μF-10μF
4) Sampling bits: 12 bits
5) Sampling speed: 200M/S
6) Test voltage: 0 to rated value (KV)
14.DC leakage current measurement (for option):
1) Output rated voltage: same as rated AC voltage output
2) Voltage accuracy: 3%
3) Leakage current range: 0-2000μA or 0-20mA
4) DC Current resolution: 1μA
5) DC current accuracy: 3%
6) It is necessary to parallel the capacitor we supplied if testing DC leakage current.
Model no |
Output Voltage/ Current (Peak) |
Load Capacity |
Control Unit |
Booster(Tank) |
Power |
Capacitance/ Freuency |
Net Dim. (cm) |
Net Wt (kg) |
Net Dim. (cm) |
Net Wt (kg) |
VLF-40TD |
40KV/30mA |
0.1Hz-0.01Hz Auto Variable Capacity:≤10µF |
46×31×50 |
35 |
-- |
-- |
1000W |
VLF-80TD |
80KV/59mA |
0.1Hz-0.01Hz Auto Variable Capacity:≤5µF at 80KV |
46×31×50 |
35 |
36x19×45 |
45 |
3000W |
Analysis of Tan delta test results (IEE400.2)
Field connection diagram
It gives 80KV output when external connecting 40KV tank.
Package for transport
1) 40KV test set:
Sr no |
Name of Commodity |
Qty |
N.W |
G.W |
Transport size (LxWxH) |
1 |
40KV test set Including 1 capacitor |
1 unit |
35 kg |
50 kg |
580x400x500mm |
Total: |
1 set |
35 kg |
50 kg |
0.12 m3 |
Packed in 1 wooden case. |
2) 80KV test set:
Sr no |
Name of Commodity |
Qty |
N.W |
G.W |
Transport size (LxWxH) |
1 |
Controll part |
1 unit |
35 kg |
50 kg |
550x400x500mm |
2 |
Tank |
1 unit |
45 kg |
69 kg |
470x430x720mm |
Capacitor |
1 unit |
4 kg |
Aluminum alloy box |
1 unit |
6 kg |
|
Total: |
1 set |
90 kg |
119 kg |
0.26 m3 |
Packed in 2 wooden cases. |
Accessories
Sr no. |
Description |
Quantity |
Remarks |
1 |
Control part |
1 |
unit |
|
2 |
Booster (Tank) |
1 |
unit |
No tank for 40KV |
3 |
Capacitor (0.04µF) |
1 |
unit |
Used as Capacity supplement, or test object for demo |
4 |
Discharge rod |
1 |
unit |
|
5 |
HV Test/Connection cables |
1 |
set |
|
6 |
Earth cable |
1 |
unit |
|
7 |
Power supply cable |
1 |
unit |
|
8 |
Fuse |
2 |
units |
|
9 |
Printer paper |
1 |
unit |
|
10 |
Operating manual |
1 |
unit |
|
11 |
Aluminium alloy box |
1 |
unit |
No this item for 40KV |
12 |
Calibration report |
1 |
unit |
|