Seconday Current Injector Relay Protection Tester Three Phase

Product Details
Customization: Available
After-sales Service: Life Time Maintenance
Warranty: Life Time Maintenance
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Manufacturer/Factory, Trading Company
Secured Trading Service
Gold Member Since 2012

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

  • Seconday Current Injector Relay Protection Tester Three Phase
  • Seconday Current Injector Relay Protection Tester Three Phase
  • Seconday Current Injector Relay Protection Tester Three Phase
  • Seconday Current Injector Relay Protection Tester Three Phase
  • Seconday Current Injector Relay Protection Tester Three Phase
  • Seconday Current Injector Relay Protection Tester Three Phase
Find Similar Products

Basic Info.

Model NO.
JBC-703
Mass Scope of Workpiece
<900kg
Type
Relay Protection
Maxcapacity
<1000KN
Accuracy Grade
0.5
Load Way
Electronic Load
Loading Method
Dynamic Load
Display
Digital
Control
Computer Control
Weight
20kg
Power Source
110V/220V
Oil Cylinder Position
Under
Transport Package
Plywood Case Outside
Specification
CE
Trademark
GOLDSOL
Origin
China
HS Code
903033200
Production Capacity
20sets/Month

Packaging & Delivery

Package Size
40.00cm * 50.00cm * 60.00cm
Package Gross Weight
35.000kg

Product Description

Advantage

1. It satisfies all requirements of field test. Model 702 tester can simultaneously output standard six-phase current and six-phase voltage with 30A/phase current and 125V/phase voltage. Connecting six phase current in parallel can acquire 180A current. The tester can not only test traditional relays and protective devices, but also test modern microcomputer-based protective devices, especially the differential protection of transformers and automatic switching devices of stand-by power supply. Testing becomes more convenient and perfect.

2. All technical parameters meet the criteria DL/T624-1997 Technical Specifications of Test Equipment Based on Micro-computer for Relaying Protection issued by the Ministry of Electric Power Industry.

3. The host machine, which has embedded high performance IPC (industrial personal computer), can run independently with its 300_600MHz main frequency, 128M memory, 6_12G hard disk and Windows XP operating system. 4. It was the first one in the industry to apply imported stainless steel panel, stainless steel keypad, touch-pad mouse, which overcomes such defects of trackball mouse as difficulty in operating and prone to damage. The TFT true color display is employed with a size of 8.

4 inch and its resolution being 800× 600. Consequently, the overall operation of the host machine becomes convenient and durable.

5. The main control board is of DSP+FPGA structure, outputting 16 bit DAC, which may generate 2000 points high density sine wave per week to fundamental wave, greatly ameliorate the quality of waveform and improve the accuracy of tester.

6. The power amplifier is Hi-Fi linear type, which can both guarantee the precision of low current and the stability of heavy current.

7. The device can directly access to PC machine through USB interface, needless of any patch cord.

8. The device can run by access to notebook computer, which is installed with a same software, needless to relearn how to operate.

9. The device has GPS synchronous testing function with embedded synchronization card (matching), which accesses to PC machine through RS232 interface, so the synchronous testing by exchanging two testers in different places can be achieved.

10. The tester is equipped with independent special DC with auxiliary voltage source output, whose output voltages are 110V (1A), 220V (0.6A), for the purpose of meeting the power need of DC relay or protective devices.

11. The tester has the function of auto-regulation by software, avoiding the calibration accuracy by opening cabinet to regulate potentiometer, so the stability of accuracy is greatly improved.

Seconday Current Injector Relay Protection Tester Three Phase
Seconday Current Injector Relay Protection Tester Three Phase
Main parameters:
                  Item                   706 (6U 6I)                     703 (4U 3I)






AC-DC  Voltage  Source
Max  Voltage  AC  6  x  125V    DC6  x  150V AC  4  x  125V    DC  4  x  150V
Maximum  Power AC  6  x  75VA    DC6  x  100VA  AC  4  x  75VA    DC  4  x  100VA 
Resolution 1mV 1mV
Accuracy 0.1%-0.2% 0.1%-0.2%
Frequency Range: 0-1000HZ
Accuracy: 0.001HZ
Range: 0-1000HZ
Accuracy: 0.001HZ
Phase Accuracy: 0.1  Degree Accuracy: 0.1  Degree
Harmonic
Distortion
≤ 0.1% ≤ 0.1%
Other Amplitude, Frequency, Phase,   separation  of  independent  by  phase,   short  circuit, over  loading, distortion, Distortion  Protection,
4th  Rd  voltage  can  be  set  to  zero-sequence  voltage  or  arbitrary  set
Amplitude, Frequency, Phase,   separation  of  independent  by  phase,   short  circuit, over  loading, distortion, Distortion  Protection,
4th  Rd  voltage  can  be  set  to  zero-sequence  voltage  or  arbitrary  set





AC-DC  Current  Source
Max  Current  AC  6  x  30A        DC  6  x  20A  AC  3  x  40A        DC  3  x  20A 
Maximum  Power AC  6  x  300VA    DC  6  x  200VA  AC  3  x  300VA    DC  3  x  200VA 
Resolution 1mA 1mA
Accuracy 0.1%-0.2%  Ultra-high-precision  low  current 0.1%-0.2%  Ultra-high-precision  low  current
Frequency Range: 0-1000HZ 
Accuracy: 0.001HZ
Range: 0-1000HZ 
Accuracy: 0.001HZ
Phase Accuracy: 0.1  Degree Accuracy: 0.1  Degree
Harmonic
Distortion
≤ 0.1% ≤ 0.1%
Other Amplitude,   frequency,   phase,   separation  of  independent  by  phase,   short  circuit, over  loading, distortion, Distortion  Protection Amplitude,   frequency,   phase,   separation  of  independent  by  phase,   short  circuit, over  loading, distortion, Distortion  Protection
Auxiliary  DC  voltage  source Output  Voltage DC110V/220V DC110V/220V
Maximum  Power 100W 100W
  The  Number  Of  Channel  8 8
  Input  Mode  Null  Input, DC5-250V, 0.5A Null  Input, DC5-250V, 0.5A
  Other Dithered  time  can  be  set Dithered  time  can  be  set
  The  Number  Of  Channel 4 4
  Output  Mode DC  0-250V, 0.5A DC  0-250V, 0.5A
Time  Measurement Range: 0.001-9.999.999S 
Accuracy: 0.001S
Range: 0.001-9.999.999S  Accuracy: 0.001S
Harmonic 2-20  times  superposition  harmonic  of  voltage  and  current  wave  can  be  set  arbitrarily  at  the  same  time. 2-20  times  superposition  harmonic  of  voltage  and  current  wave  can  be  set  arbitrarily  at  the  same  time.
Size 470mm  x  405mm  x  185mm 450mm  x  400mm  x  185mm
Weight 20  Kgs 16  kgs
Power AC220V  ±   10%50HZ  ±   10%10A  AC220V  ±   10%50HZ  ±   10%10A

Seconday Current Injector Relay Protection Tester Three Phase
Seconday Current Injector Relay Protection Tester Three Phase
Accessaries

1.Portable aluminium alloy box: 1 unit;
1.Power supply cable:  1 unit; 
2.CD drive:   1 unit;
3.USB connection:  1 unit;
4.Test cable:  1 set (Current wires 6 units/set; Voltage wires 6 units/set;
  Switch test wores 6 wires/set);
5.Test clip and accessary: 1 set;  
6.Fuse: 3units/10A Fuse; 3 units/3A fuse
7.Certificate: 1 unit 
8.Calibration Report: 1 unit
9.Operating manual: 1 unit


Seconday Current Injector Relay Protection Tester Three Phase








 