I. Intruduction
TAG-8600 High voltage detector 500KV, which is suitable for testing 220V to 500KV live transmission line, phase tests and phase sequence tests for substations, with functions of phase testing, phase sequence testing, electrical inspection. With strong anti-interference ability, in line with (EMC ) standards, adapt to a variety of electromagnetic interference occasions. High voltage phase signal will be taken out by the collector, discharge directly after treatment. Received by instrument and compare the phase, and identify the results. This product is wireless transmission, safe, reliable, fast and accurate, adapt to a variety of phase testing occasions. Its main advantage is without the wire which connect two grids (power source) , distance up to 200M and could trough enclosure or partition plate, improve the safety, without the limitation by terrain and the structure of the equipment , easy to operate, only need one person to operate and one person to supervise.
II. Safety
1.When testing at field, keep a safe distance as per high-voltage power sector standard operation.
2. It has standard configuration of insulating rod 5 m, corresponding to the voltage class ≤ 500kV,
3.When phase clarification operating, holder should not exceed insulated rod handle.
Self-detecting whether the instrument is normal
Detecting live display of high voltage switchgear (LV detecting)
Detecting transmission line (HV detecting)
III. Advantage
1.Use high capacitive non-maintenance lithium battery to supply power, special for field test.
2. Long transmission distance, up to 200M.
3. LCD display phase ,waveform, frequency , safe and reliable.
4. Telescopic insulation bar, easy to use.
5. Portable receiver with non-skid treatment.
6. uses advanced technique, small in volume, light in weight
IV. Technical Parameter
1.Phase error : ≤5 °.
2.Frequency accuracy: ± 0.1Hz.
3.Measuring voltage class: 220V~500KV.
4.Transmission distance between the transmitter and Receiver: > 130 m;
Maximum distance between 2 transmitters: 260 meters.
5.A class judgment result (in-phase, out-phase):
phase difference ≥30°: out of phase;
phase difference <30°: in-phase.
6.Live voice prompt, Boy"in-phase" and Girl "out of phase".
7.LCD simultaneously displays 2 lines' phase, frequency, waveform and vector diagram.
8.Receiver (host) shows battery level, and automatic shutdown if no operating in a half hour.
9.Transmitter and receiver are built-in rechargeable lithium battery.
10.High voltage electrical detection and approval phase sequence dual purposes.
11.Leakage current when HV measurement: <10µA.
12.Transmitter operating power <0.1W, Receiving operating power <0.3W.
13.Receiver lithium battery capacity:2200mAH, transmitter battery capacity:350mAH.
14.Operating environment: -35ºC ~ + 45 ºC, humidity ≤95% RH.
15.Storage environment: -40ºC ~ + 55 ºC, humidity ≤95% RH.
16.Weight: about 5KG.
17.Package dimension: length 71cm * width 26cmm * height 11cm.
V. Additional remark
Vlotage Class |
Operating remark |
Remark |
500KV |
Connected Transmitters to Insulation rod(5m), hooking HV line,start the receiver |
Normal |
330KV |
Connected Transmitters to Insulation rod(4m), hooking HV line,start the receiver |
Normal |
220KV |
Connected Transmitters to Insulation rod(3m), hooking HV line,start the receiver |
Normal |
110KV |
Connected Transmitters to Insulation rod(3m), hooking HV line,start the receiver |
Normal |
35KV |
Connected Transmitters to Insulation rod(3m), hooking HV line,start the receiver |
Normal |
10KV(Naked) |
Connected Transmitters to Insulation rod(3m), hooking HV line,start the receiver |
Normal |
10KV(with insulation cover) |
Connected Transmitters to Insulation rod(3m), hooking HV line,start the receiver |
Turn on the transmitter, off the transmitter after finishing |
380V/220V |
Connected commercial power special line to Transmitters,start the receiver |
Using commercial power special line |
Switch induction (~5V) |
Connected switch inductive cable to the transmitters and start the receiver |
Using switch inductive power cable |
VI. Accessaries
Sr no. |
Description |
Quantity |
1 |
Aluminium alloy box |
1 unit |
2 |
Receiver (Host) |
1 unit |
3 |
Transmitter |
2 units(X,Y, each one) |
4 |
Extension-type insulation road(3m) |
2 units |
5 |
Charger |
2 units |
6 |
Pointed end |
2 units |
7 |
Commercial power special cable |
2 units |
8 |
Switch inductive power cable |
2 unis (Optional) |
9 |
Operating manaul |
1 unit |
10 |
Calibration |
1 unit |