Hubei, China
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Consumer Electronics, Electrical & Electronics, Industrial Equipment & Components, ...
Management System Certification:
ISO 9001
Main Markets:
North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, ...
OEM/ODM Availability:
Yes
OEM/ODM Service
Overseas Agent / Branch

Potential Transformer Analyzer, Current Transformer Tester, CT and PT Tester manufacturer / supplier in China, offering CT PT Analyzer (GLDL-404), Vlf High Voltage Generator 90kv, C & Tan Delta Tester and so on.

Gold Member Since 2012
Audited Supplier

CT PT Analyzer (GLDL-404)

Get Latest Price
Min. Order: 1 Piece
Port: Wuhan, China
Production Capacity: 20 Set/Month
Payment Terms: T/T
Connectors: USB
Test Mode: Saved Test
Certification: CE
Customized: Non-Customized
Color: Black
Transport Package: Plywood Case

You Might Also Like

Loading...

Basic Info

Model NO.: GLDL-404
Trademark: GOLDSOL
Specification: CE
Origin: China
HS Code: 9030339000

Product Description

Application
Testing Current transformer:
1. Excitation curve and parameters test
2. Turns ratio test
3. Ratio and phase error test
4. Polarity mark check
5. Coil resistance measurement
6. Secondary loop burden measurement
7. Error line curve test for protection CT
8. Transient CT parameters test
9. CT nameplate guess

CT PT Analyzer (GLDL-404)

Testing Voltage transformer:
1. Excitation curve test
2. Turns ratio test
3. Polarity test
4. Secondary burden test
5. Coil resistance test

CT PT Analyzer (GLDL-404)

Applications for CTPT analyzer:
1. CT nameplate check
2. CT parameters check in work burden
3. CT transient parameters analysis
4. CT ratio and phase error calibration
5. PT routine test

CT/PT analyzer technical index
1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2 Power supply: AC220V± 10%, 50Hz/60Hz± 10%
3 Power output: 0.1~125V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output: 300VA
6 Maximum knee voltage measurement; 45kv
7 Current measurement:
Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
Error <± 0.1%+0.01%FS
8 Voltage measurement:
Range: 0~200 V (automatically change range in 1V/10V/70V/200V)
Error < ± 0.1%+0.01%FS
9 Turns ratio measurement:
Range: 1~30000,
1~1000 error<0.05%
1000~2000 error<0.1%
2000~30000 error<0.2%
10 Phase measurement: Error: ± 2min, resolution: 0.01min
11 Coil resistance measurement:
Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error< 0.1%RDG+0.01%FS
Maximum resolution: 0.1MΩ
12 Temperature measurement: -50~100 Celsius degree, error<3 Celsius degree
13 CT Secondary burden:
Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution 0.001ohm
14 PT Secondary burden:
Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error <0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15 Saved data groups: >1000groups
16 Work condition: Temperature: -10ºC~50ºC, moist: ≤ 90%
17 Size: 485mm*356mm*183mm
18 Weight: <15Kg